Need some advice? Get in touch today to discuss your needs.

make an enquiry

,

JP04 Tied Rubber Bellow

Specification

Untied E.P.D.M. rubber bellows with nylon reinforced body and steel reinforced collar. Fitted with zinc plated carbon steel swivel flanges. Drilled to BS. 4504 NP16.

Application

Stourflex tied rubber bellows are designed to accommodate misalignment and lateral movement. They are also used to reduce noise and vibration from pumps and reciprocating machinery. They are suitable for chilled water and L.T.H.W. systems.

L.T.H.W. – 90°C

Sizes 32mm – 300mm

Maximum working pressure 10 bar.

Sizes 350mm – 600mm

Maximum working pressure 6 bar.

C.H.W. – 6°C/12°C

Sizes 32mm – 300mm

Maximum working pressure 16 bar.

Sizes 350mm – 600mm

Maximum working pressure 10 bar.

Stourflex rubber bellows should not be used at both their maximum working temperature and pressure respectively. Maximum test pressure = 1.5 x working pressure or 1.5 x flange rating, whichever the lower.

Lagging

Stourflex are now able to offer a tailor made flexible lagging jacket to help reduce heat losses on LTHW systems and heat gains & condensation on CHW systems. Please ask for more information.

Download data sheet
JP04 rubber bellows

our technical specifications

Our JP04 Tied Rubber Bellow specifications

Part numberN.B. (mm)Installed Lengths (mm)Number Of Tie Bars (mm)Lateral Movement (mm)
JP04-32-163295 / 15029 / 14
JP04-40-164095 / 15029 / 14
JP04-50-1650105 / 150210 / 14
JP04-65-1665115 / 150211 / 14
JP04-80-1680150214
JP04-100-16100150214
JP04-125-16125150 / 170213 / 14
JP04-150-16150150 / 180213 / 14
JP04-200-16200150 / 205214 / 22
JP04-250-16250205222
JP04-300-16300205422
JP04-350-16350205422
JP04-400-16400205422
JP04-450-16450205422
JP04-500-16500205422
JP04-600-16600265422

Supplied length may vary. Tolerance +/-5%

Alternative flange drillings and materials are available on request.

Stourflex products should be installed in accordance with our fitting instructions.

Stourflex rubber bellows should be periodically inspected and replaced if any deterioration is evident.

Download data sheet