JP114 Stainless Steel Axial Expansion Joint Screwed

Introducing the JP114 Stainless Steel Axial Expansion Joint Screwed – crafted from durable 316 stainless steel with precision-fit BSPT end connections. Perfect for high-pressure, high-temperature applications (up to 120ºC), it accommodates axial movement in pipework systems for DHWS, LTHW, MTHW, hot liquids, and gases. Now available with flexible lagging jackets to reduce heat loss and condensation.

Product Information

Now Available With Precision Fit Flexible Lagging Jackets To Suit JP114.

Specification

Axial expansion joint consisting of stainless steel grade 316 bellows assembly fitted with stainless steel grade 316 male B.S.P.T. end connections.

Application

Stourflex axial expansion joints are designed to accommodate pipe movements in an axial plane (straight runs) due to thermal expansion. They are suitable for L.T.H.W, M.T.H.W, condensate and other hot liquids and gasses.

The Type JP114 is manufactured to have all stainless steel wetted surfaces and is particularly suitable for copper or stainless steel pipework. The type JP114 is recommended for use on high pressure applications or installations where guiding proves difficult.

  • Maximum working temperature 120ºC.
  • Maximum working pressure 10 bar at 200ºC.
  • Stourflex axial expansion joints should not be used at both their maximum working temperature and pressure respectively.
  • Maximum test pressure =1.5 x working pressure or 1.5 x end connection rating, whichever the lower.

Lagging

Stourflex are now able to offer a tailor made flexible lagging jacket to help reduce heat losses on LTHW systems and heat gains & condensation on CHW systems. Please ask for pricing or more information.

Need next day delivery?

Typically we can provide next day delivery nationwide

Technical specifications

Our JP114 Stainless Steel Axial Expansion Joint Screwed specifications.
Part numberN.B. (mm)Total movement
(-mm)
Overall length (mm)External sleeve outside diameter (mm)Effective area (Cm²)Working pressure @200°C (bar)Cold test pressure (bar)
JP114-1515452604071015
JP114-2020452604071015
JP114-25254528550121015
JP114-32324532060171015
JP114-40404532075271015
JP114-50504532075271015

Further Information

Polished aluminium external protective sleeve complete with movement indicator and limit clip fitted as standard.

Remove limit clip after installation.

Supplied at maximum length do not extend.Expansion joint convolutions should be protected from damage caused by rotational forces during installation.

Axial expansion joints must be securely anchored and adequately guided to ensure their correct performance.

Omitting anchors and guides may result in failure of the system.

Please refer to guidance notes for the correct use and installation of Stourflex axial expansion joints.

All Stourflex products should be installed in accordance with our fitting instructions.

Latest Projects

Bankside Case Study
A 390,000 sq ft residential scheme and comprises 217 homes in buildings ranging from 12 to 24 storeys.
JLR case study
Interserve engaged our team for expertise in vibration and noise reduction, air dirt removal, and water treatment at the £550m JLR i54 plant in Wolverhampton, designed to produce an engine every 36 seconds.
Birmingham council case study
As part of the £65m 3 Arena Central development in Birmingham, our team designed and supplied thermal expansion solutions, rooftop supports, and installation services, with continued after-sales support and site visits.
Stourflex partnered with T Clarke on London’s iconic The Shard, supplying high-performance rubber bellows to provide vibration isolation for critical pump systems, helping ensure reliable operation, reduced noise transmission and enhanced mechanical services performance throughout the landmark development.
At Airbus Broughton, our team worked with NG Bailey to design and supply bespoke rooftop support systems for AHUs and chillers, overcoming tight roof space and pitch constraints through a tailored engineered configuration.
At The Macallan distillery, our team supported Forsyth by providing angular and lateral expansion joints, accommodating the unique outward growth of circular steam and condensate pipework alongside straight pipe connections.
Working with Lorne Stewart on this landmark Grade II listed tower, our team designed a tailored expansion solution, combining axial and lateral joints with compatible anchors and guides to suit the high-pressure stainless steel refurbishment.
For this highly complex project, our team delivered a tailored high-pressure steam expansion solution, providing verified anchor-force calculations and innovative Sikla Simotec Ultraglide support systems to minimise structural impact on existing brickwork, floors and walls.