Now Available With Precision Fit Flexible Lagging Jackets To Suit JP114.

Specification

Axial expansion joint consisting of stainless steel grade 316 bellows assembly fitted with stainless steel grade 316 male B.S.P.T. end connections.

Application

Stourflex axial expansion joints are designed to accommodate pipe movements in an axial plane (straight runs) due to thermal expansion. They are suitable for L.T.H.W, M.T.H.W, steam, condensate and other hot liquids and gases.

The Type JP114 is manufactured to have all stainless steel wetted surfaces and is particularly suitable for copper or stainless steel pipework. The type JP114 is recommended for use on high pressure applications or installations where guiding proves difficult.

  • Maximum working temperature 250ºC.
  • Maximum working pressure 10 bar at 200ºC.
  • Stourflex axial expansion joints should not be used at both their maximum working temperature and pressure respectively.
  • Maximum test pressure =1.5 x working pressure or 1.5 x end connection rating, whichever the lower.

Lagging

Stourflex are now able to offer a tailor made flexible lagging jacket to help reduce heat losses on LTHW systems and heat gains & condensation on CHW systems. Please ask for pricing or more information.

Download data sheet
JP114 expansion joint

our technical specifications

Our JP114 Stainless Steel Axial Expansion Joint Screwed specifications

Part numberN.B. (mm)Total movement
(-mm)
Overall length (mm)External sleeve outside diameter (mm)Effective area (Cm²)Working pressure @200°C (bar)Cold test pressure (bar)
JP114-1515452604071015
JP114-2020452604071015
JP114-25254528550121015
JP114-32324532060171015
JP114-40404532075271015
JP114-50504532075271015

Polished aluminium external protective sleeve complete with movement indicator and limit clip fitted as standard.

Remove limit clip after installation.

Supplied at maximum length do not extend.

Expansion joint convolutions should be protected from damage caused by rotational forces during installation.

Axial expansion joints must be securely anchored and adequately guided to ensure their correct performance.

Omitting anchors and guides may result in failure of the system.

Please refer to guidance notes for the correct use and installation of Stourflex axial expansion joints.

All Stourflex products should be installed in accordance with our fitting instructions.

Download data sheet